D-2 Fuel

Quality of D2 Fuel L0.2/62 delivered under contracts should meet requirements of GOST 305-82, switching, but not limited to requirements of the below-mentioned specifications.

Specification of GASOIL 02 L-O.2-62 (GOST 305-82)

Component Unit MIN. MAX
Density at 20°C  kg/m3 0.87
Color 1.0 2.0
Flash Point, Pmcc(1)  °C 57  66
Kinematics Viscosity @ 20 C CST 3.0 6.0
Pour point  °C (*)  -10
Cloud point  °C (*)  -5
Mercaptan sulphur margin  %  0.01
Acidity mg /100 cm3 5
Iodine number  G/100g 6
Ash  %wt 0.01
Total sulphur  %wt  0.5
Copper corrosion (3 hrs at 50°C) 1A
CCR ON 5% Residue  %wt 0.20
Cetane index  45
Distillation Range
50% Recovery Volume °C 280
90% Recovered Volume °C 360
Bacteria MBC Fiber / Lt 500
Bacteria CFU Fiber / Lt 1000

(1) Pensky Martin Closed Cup Test
* SUMMER FROM TO OCTOBER (PP – 5.0°C) (CP – 5.0°C)
* WINTER FROM TO NOVEMBER TO FEBRUARY (PP – 10.0°C) (CP – 5.0°C)